
Liquid separators in ammonia heat pumps: four pitfalls
Four faults we find in the low-pressure separators of air-to-water heat pumps, and what to check
Contents
Why read this
Many ammonia heat pumps get the same liquid separator as a freezing plant. An air-to-water heat pump evaporates at around 0 °C instead of −40 °C, and at that temperature the separator behaves differently. This article describes the four faults we find most often on built plants, with a 10 MW heat pump as the example.
Why the heat pump is different
At 0 °C ammonia vapour is more than five times denser than at −40 °C. As a result, droplets fall more slowly, the liquid injection hits harder and the gas carries liquid along more easily (figure 1). The rules of thumb from freezing plants do not apply at 0 °C.

The example: an air-to-water heat pump of about 10 MW heat output, 7 MW from the air, 0 °C evaporating temperature. Our separator tool sizes a horizontal vessel of 2,350 × 7,100 mm, with a wet return at each end and the dry suction in the middle (figure 2). The compressors take 6,800 m³/h of vapour, and the pumps circulate 125 m³/h.

1. Gas space sized with figures from freezing applications
Symptom: liquid at the compressors, mostly on warm days at full load.
At 0 °C droplets fall about a third more slowly than at −40 °C, and good practice asks for a larger margin at higher evaporating temperatures. Together, this limits the vapour velocity to 0.58 m/s, against 1.45 m/s in a freezing plant: about 40 % as fast.
In the example the vapour flows at 0.52 m/s, 90 % of the limit. Checked against figures from freezing applications, the vessel would appear only a third used, which invites a smaller vessel.
Check: the warmest operating point at full compressor speed. At full speed the compressor takes the same volume flow at every evaporating temperature, and droplets fall more slowly as the evaporating temperature rises.
2. Liquid injection
Symptom: carry-over although the vessel is large enough.
The mixture in the wet returns and the make-up is five times denser at 0 °C than at −40 °C, so at the same velocity the jet hits five times harder. In the example the wet returns run at 4.4 m/s, which hits as hard as 10 m/s at −40 °C. A jet that hits the liquid or a wall head-on breaks the liquid up into mist, and the mist does not settle again.
The angle matters. A make-up pipe that ends above the liquid sprays the liquid into the gas space. Turned through a short bend along the shell, 15° down, the jet meets the wall at a slant and the liquid runs down the wall (figure 3). Each wet return is turned towards its own end of the vessel, also 15° down.

Check:
- injection velocities for the heat pump’s conditions, not figures from freezing applications;
- no jet aimed at the liquid surface, the drop leg or the dry suction;
- bends above the highest liquid level, also during a defrost.
3. Dry suction velocity
Symptom: liquid at the compressors although the vessel separates well.
Under the mouth of the dry suction the gas accelerates from the low velocity in the vessel to the velocity in the pipe. Droplets that reach this zone and fall more slowly than the gas rises are lifted into the pipe. The smaller the dry suction, the stronger this vacuum cleaner effect close to the mouth.
We ran a screening flow calculation (CFD) of the vapour for the example with our tool, on a finer grid than its standard setting: DN600 at 7 m/s as sized, and DN400 at 16 m/s (figure 4):
- 0.3 m below the mouth the gas rises at 2.7 m/s with DN400, against 2.0 m/s with DN600;
- 0.5 m below the mouth it rises at 1.0 m/s against 0.8 m/s, and lifts droplets of up to 0.4 mm against 0.3 mm.

The difference between the two sizes is largest close to the mouth. With both, the gas lifts 0.1 mm droplets from about 0.8 m below the mouth. A small dry suction therefore makes carry-over more likely when liquid comes close to the mouth:
- a level raised by a defrost or a load change, or foam, that reaches the zone under the mouth;
- liquid injection or a splash aimed at the mouth or close to it.
Check:
- the dry suction velocity at the warmest operating point;
- enough height between the mouth and the highest liquid level (1.1 m in the example);
- the mouth away from the liquid injection: with two wet returns, in the middle.
4. Drop leg to the pumps
Symptom: pumps that cavitate, lose head or trip, often when the compressors ramp up.
Gas bubbles in the drop leg must rise back into the vessel against the liquid flowing down. That only works at low velocity. In the example the drop leg must be DN300 (0.46 m/s). Sized as a pump suction line it would be DN250 at 0.65 m/s, and it would carry gas down to the pumps. The outlet also needs liquid above it: at least 200 mm at the lowest level, so that the drop leg can vent itself and no vortex pulls gas in.
At 0 °C the liquid height gives less protection: one metre of liquid covers a drop in suction temperature of 0.4 K, against 1.8 K at −40 °C.
Check:
- the drop leg sized for the full pump flow at low velocity, not as a pump suction line;
- at least 200 mm of liquid above the outlet, and a vortex breaker;
- a vent line from the pump suction back to the vessel.
Our view
An ammonia heat pump can use the same type of separator as a freezing plant, but the separator must be sized for the heat pump’s evaporating temperature. On a built plant, the checks above can show where carry-over or unstable pumps come from. The fix can be small: a bend on the liquid injection, a second nozzle, a new dry suction or a larger drop leg.
Key findings
- A separator sized with figures from freezing applications is too small: at 0 °C the vapour may flow only about 40 % as fast as at −40 °C.
- At the same velocity, the liquid injection hits five times harder at 0 °C than at −40 °C. Turn the make-up along the shell, 15° down.
- A small dry suction strengthens the suction under its mouth: at 16 m/s instead of 7 m/s the gas 0.3 m below the mouth rises at 2.7 instead of 2.0 m/s. Keep liquid and the liquid injection away from the mouth.
- A drop leg sized as a pump suction line carries gas to the pumps. Size it so that it vents itself, and keep at least 200 mm of liquid above it.






